
INSTRUCTIONSUltraviolet Flame Detection SystemR7404 ControllerC7050 Detector7/97 Form 95-8242-04To navigate throughthis document, clickon the “Bookmar
produce a count. If the x- or gamma ray flux is sufficient toproduce a count rate higher than the system sensitivity set-ting, an undesired response
The system can be adjusted to various sensitivity levelsby programming the controller to respond at a pre-deter-mined detector tube count rate. This
Since moisture can be detrimental to electronic devices,it is important that moisture not be allowed to come incontact with the electrical connections
ward to prevent the cone of vision from scanning thehorizon, since the detectors can be affected by longduration lightning flashes or distant arc weld
IMPORTANTUse only DE1888 sensor modules with the C7050Detector. The jumper plug must not be installed onthe UV sensor module used with the R7404 Cont
tioning normally, but will not produce the desiredoutput in response to the input conditions. (Someof the switches are not used and should be left in
2. Controller Sensitivity — Rockers 3-1 to 3-4Rockers 3-1 to 3-4 are used to program controllersensitivity in 8 cps increments.3-1 closed — 8 cps3-2 c
4. Output Latching/Non-latching — Rocker 4-1closed — non-latchingopen — latchingNOTEThe zone and fire logic outputs will latch whenturned on if rocker
NOTEExternal equipment that can generate transientswhen switching (such as relays) must have a tran-sient suppression device (diode) connectedacross t
17 95-82421234567891011121314151617181920212223242526272829303132 + – (A) +290 VDCB - INPUT 1B - INPUT 2B - INPUT
Table of ContentsSYSTEM APPLICATION ...1FEATURES ...
The Data Bus terminals (56 to 63) and the DMA (directmemory access) and Data Strobe terminals (28 to 32)provide external access to the microprocessor,
— Lower display indicates a “1.” (If any other num-ber appears, refer to the “Troubleshooting” sec-tion of this manual.)2. Push and hold the TEST/ACC
DETECTOR COUNT TEST1. Place the keylock switch in the TEST position.— The SYSTEM STATUS display shows the number“1.”— The upper displays show the dete
4. Repeat the test for all detectors in the system.5. After all detectors have been checked, reset thesystem by turning the keylock switch to the RESE
DEVICE REPAIR AND RETURNPrior to returning devices or components, contact thenearest local Detector Electronics office so that an RMI(Return Material
Detector Electronics Corporation466 Conchester HighwayAston, Pennsylvania 19014 USATelephone (610) 497-5593Facsimile (610) 485-2078Detector Electron
Det-Tronics BeneluxCosterweg 5NL-6702 AA WageningenTHE NETHERLANDSTelephone 31 (0)317 497625Facsimile 31 (0)317 427308117333 MoscowGubkina St, d.3Gi
—Air Shields provide a continuous flow of clean airacross the viewing window of the detector to reducethe accumulation of certain types of airborne co
APPENDIX [Factory Mutual Research Corporation (FMRC) Approval Description]R7404 CONTROLLER AND C7050 UV FLAME DETECTOR• Automatic Fire Alarm Signaling
INSTRUCTIONSUltraviolet Flame Detection SystemR7404 ControllerC7050 Detector7/97 Form 95-8242-04
SYSTEM APPLICATIONThe Det-Tronics model R7404 Controller and C7050Detector provide fast, reliable flame detection in a widevariety of applications. T
Solid Materials—Munitions production such as illuminating flare materi-al, TNT, and other propellants—Powder coating boothsOther Processes—Paint Spray
The output of the detector consists of a series of voltagepulses or “counts.” The frequency of these pulses isdirectly proportional to the intensity
tem. The main loop of the operating program continu-ously cycles through the Automatic Optical Integrity test,checking each detector and its wiring.
tors to fulfill voting requirements, and represents the bestbalance between reliability of fire detection and freedomfrom false actuation due to indiv
resistance is 16.14 ohm/1000 ft. or 53.0 ohm/km.) TheR7404 Controller will accommodate up to 16 detectors.The detectors can be located up to 2000 fee
DETECTOR SENSITIVITYThe UV flame detector responds to radiation over wave-lengths of 185 to 245 nanometers (1850 to 2450angstroms). Figure 6 illustra
Komentarze do niniejszej Instrukcji