DESCRIPTIONThe DEC-THZ Toxic Gas Transmitter is a Class I,Division 1 approved device when used with anapproved sensor, and is compatible with the enti
SPECIFICATIONSDETECTION RANGE—Depends on sensor selected. Refer to form number90-1079 (Specification Data sheet for Det-Tronicselectrochemical sensor
INSTALLATIONDETECTOR LOCATION AND ORIENTATIONThe gas sensor used with the THZ transmitter is a dif-fusion-based gas sensor. Therefore, it must contac
CONFIGURATION USING HART COMMUNICATIONThe DEC-THZ gas detector is shipped from the facto-ry pre-configured. If it is necessary to change anyHART con
Important Calibration Notes•Ensure that the transmitter is properly programmedfor the gas concentration being used for calibration.• Ensure that only
MAINTENANCEROUTINE MAINTENANCEThe DEC-THZ requires no routine maintenance,except for periodic checks to ensure proper calibra-tion. The frequency of
5. Be sure that the O-ring inside the sensor base isin good condition, then re-install the cap. Tightenonly until snug. Do not over tighten.6. Re-ap